Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | ISM15_LD_1 ISM15_LD_2 ISM15_LD_3 |
ISM25_LD_1 ISM25_LD_3 |
|
Rated Data | Rated voltage (Ur) | 15 kV | 27 kV |
Rated current (Ir) | to 1000 A | to 800 A | |
Rated power frequency withstand voltage (Ud) | 36 kV | 60kV | |
Rated lightning impulse withstand voltage (peak) (Up) | 95 kV | 125 kV | |
Rated short-circuit breaking current (Isc) | to 20 kA 6) | to 16 kA 6) | |
Rated peak withstand current (Ip) | to 52 kA | to 42 kA | |
Rated short-time withstand current (Ik) | to 20 kA | to 16 kA | |
Rated duration of short circuit (tk) | 4 s | ||
Rated frequency (fr) | 50 / 60 Hz | ||
Switching Performance |
Mechanical life 5) (CO-cycles) | 50000/1500002) | 30000 |
Operating cycles 5), rated current (CO-cycles) | 50000/1500002) | 30000 | |
Maximum number of CO-cycles per hour | refer to CM | ||
Operating cycles 5), rated-short circuit breaking current | 100 | ||
Closing time 3), with CM_1501_01 - not more than | 30 ms | 35 ms | |
Opening time 3), with CM_1501_01 - not more than | 15 ms | ||
Break time 3), with CM_1501_01 - not more than | 23 ms | ||
Rated operating sequence (CM_1501_01) | O-0.3s-CO-10s-CO | ||
Standards | Design class with regard to severity of service conditions in accordance with IEC 932 | Class 1 | Class 0 |
Standards | IEC 62271-100, GB 1984-2003 ANSI C37.04, C37.06, C37.09, C37.09a |
||
Mechanical vibration withstand capability according to IEC 721-3-4 | Class 4M4 | ||
Other data | |||
Resistance of main circuit | < 40 µOhm | ||
Weight (depending on PCD) for three-phase ISM | 34, 36, 37 kg | 33, 36, 38, 39 kg | |
Weight for single phase ISM | 13 kg | 14 kg | |
Type of driving mechanism | Monostable magnetic actuator | ||
Design, Switching Capacity of Auxiliary Contacts |
Number of available auxiliary contacts for three-phase ISM | 6 NO + 6 NC | |
Number of available auxiliary contacts for single-phase ISM | 2 NO + 2 NC | ||
Minimum current for 12 V AC / DC, ohmic load | 100 mA | ||
Minimum current for 12 V AC / DC, inductive load (t=20 ms, cosj =0,3) | 100 mA | ||
Maximum current for 30 V DC, ohmic load | 5 A 4) | ||
Maximum current for 30 V DC, inductive load (t=20 ms) | 3 A | ||
Maximum current for 60 V DC, ohmic load | 0.9 A | ||
Maximum current for 60 V DC, inductive load (t=20 ms) | 0.9 A | ||
Maximum current for 125 V DC, ohmic load | 0.5 A | ||
Maximum current for 125 V DC, inductive load (t=20 ms) | 0.03 A | ||
Maximum current for 250 V DC, ohmic load | 0.25 A | ||
Maximum current for 250 V DC, inductive load (t=20 ms) | 0.03 A | ||
Maximum current for 125 V AC, ohmic load | 5 A 4) | ||
Maximum current for 125 V AC, inductive load (cosj =0,3) | 5 A | ||
Maximum current for 250 V AC, ohmic load | 5 A 4) | ||
Maximum current for 250 V AC, inductive load (cosj =0,3) | 5 A |