Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated Data | ||
---|---|---|
Rated voltage (Ur), up to | 15.5kV | 27kV |
Rated continuous current (Ir) | 800A | |
8-hour overload current | 960A | |
Rated power frequency withstand voltage (Ud), 1 min dry | 60kV | |
Rated power frequency withstand voltage (Ud), 10s wet | 55kV | |
Rated lightning impulse withstand voltage closed contacts/open contacts (peak) (Up) | 150/125kV | |
Rated short-circuit breaking current (Isc) | 16kA | 12.5kA |
Rated short-circuit making current, peak | 41.6kA | 32.5kA |
Rated short-time withstand current, 4s (Ik) | 16kA | 12.5kA |
Rated frequency | 50/60Hz |
Switching Performance | |
---|---|
Mechanical life (CO cycles) | 30,000 |
Operating cycles, rated current (CO cycles) | 30,000 |
Electrical endurance, breaking current (O-CO cycles) | 100 |
Closing time1 | <40ms |
Opening time1 | <15ms |
Interrupting time, for 50/60 Hz1 | <25/23 ms |
Rated operating sequence | O-0.2s-CO-1.5s-CO-2s-CO-2s-CO2 |