Customization: | Available |
---|---|
Type: | Power |
Structure: | Open Frame |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Standards | Design verified and Type-tested switchgear assemblies | GB/T 7251.1/12-2013, IEC 61439-1/2, EN 61439-1/2, DIN_VDE 0660, Part 500 BS 5486, UTE 63-412 |
|||
Test certificates | (CCC) China Compulsory Product Certification | China Quality Certification Centre | |||
Type test | ASTA, Shanghai Testing & Inspection Institute For Electrical Equipment Co. Ltd |
||||
Short-circuit withstand strength test | ASTA, Shanghai Testing & Inspection Institute For Electrical Equipment Co. Ltd |
||||
Resist to accidental arcs acc. to IEC 61641 and part 508 of VDE0660 | ASTA, Great-Britain | ||||
Classification Society Certification (shipping) | Gemanischer Lloyd | ||||
Earthquake Test for Security Areas in Nuclear Power Stations | China National Center of Quality Supervision and Test for Electrical Apparatus Products/DRL German Research |
||||
Electrical data | Rated voltages |
Rated insulation voltage Ui | up to 1000V AC, 3 P, 1500V DC* | ||
Rated operating voltage Ue | up to 690V AC, 3 P, 750V DC* | ||||
Rated impulse withstand voltage Uimp | 6/8/12 kV* | ||||
Overvoltage category | II/III/IV* | ||||
Degree of pollution | 3 | ||||
Rated frequency | up to 60 Hz | ||||
Copper Busbars Rated current Ie Rated peak withstand current Ipk Rated short-time withstand current Icw |
up to 6300 A | ||||
up to 220 kA | |||||
up to 100 kA | |||||
Distribution bars | Rated current Ie | up to 2000 A | |||
Rated peak withstand current Ipk | up to 220 kA | ||||
Rated short-time withstand current Icw |
up to 100 kA | ||||
Arc proof Rated operating current Criterion (IEC 61641) |
up to 690 V | ||||
up to 100 kA | |||||
300 ms | |||||
1 to 7 | |||||
Mechanical characteristics | Dimensions Sections and frames Basic grid size |
DIN41488 | |||
2200 mm | |||||
400, 600, 800, 1000, 1200 mm | |||||
800, 1000, 1200 mm | |||||
E=25 mm acc. to DIN 43660 | |||||
Surface protection |
Frame Enclosure |
Alu-zinc coated | |||
Alu-zinc coated/Zinc coated/Non-metal | |||||
Alu-zinc coated/Zinc coated | |||||
Alu-zinc coated and Powder coated RAL 7035, light | |||||
Degrees of IEC 529 protection of plastic Halogen-free, self-extinguishing components flame retardant, CFC-free Internal subdivision |
up to IP54 | ||||
DIN VDE0304 Part 3 | |||||
IEC707 | |||||
up to Form 4 |