8djh Gas-Insulated Medium Voltage Switchgear

Product Details
Customization: Available
Certification: VDE
Shell Material: Steel Plate
Gold Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Fast Delivery
The supplier can deliver the goods within 15 days
Customization from Designs
The supplier provides design based customization services
ODM Services
The supplier provides ODM services
Management Certification
The supplier has quality management system certification, including:
ISO9001:2015 certificate
ISO45001:2018 certificate
ISO14001
to see all verified strength labels (14)
  • 8djh Gas-Insulated Medium Voltage Switchgear
  • 8djh Gas-Insulated Medium Voltage Switchgear
  • 8djh Gas-Insulated Medium Voltage Switchgear
  • 8djh Gas-Insulated Medium Voltage Switchgear
  • 8djh Gas-Insulated Medium Voltage Switchgear
  • 8djh Gas-Insulated Medium Voltage Switchgear
Find Similar Products
  • Overview
  • Product Description
  • Detailed Photos
  • Specification
Overview

Basic Info.

Model NO.
8DJH
Voltage Level
Medium Voltage
Installation
Fixed
Structure
Cabinet
Current
AC
Rated Voltage
7.2/12kv
Rated Frequency
Hz
Rated Continuous Current
630A
Rated Short-Time Withstand Current
21ka,3s
Rated Filling Level
1.6kpa
Transport Package
Wood Box Transportation
Specification
Optional
Trademark
Siemens
Origin
China

Product Description

Product Description
       8DJH 12 switchgear is a factory-assembled, type-tested, 3-pole metal-enclosed single-busbar switchgear for indoor installation. 8DJH 12 switchgear is used in public and industrial energy systems of the secondary distribution level, e.g. in
 
• Secondary transformer substations of power supply system operators
• Utilities transfer substations for business enterprises
• Installations of building supply technologies
• Water and sewage treatment plants
• Underground railway stations, railway stations, airports
• Charging stations for electric vehicles
• Generating plants for renewable energies (biomass, hydro power, wind turbines, solar parks).
Detailed Photos
8djh Gas-Insulated Medium Voltage Switchgear8djh Gas-Insulated Medium Voltage Switchgear8djh Gas-Insulated Medium Voltage Switchgear8djh Gas-Insulated Medium Voltage Switchgear

8djh Gas-Insulated Medium Voltage Switchgear

Specification
Electrical data of the switchgear Rated voltage Ur    kV 7.2  12 
Rated insulation level
  Rated short-duration power-frequency withstand voltage U:
- phase-to-phase, phase-to-earth, open contact gap
- across the isolating distance

   kV
   kV

20
23

28
32
  Rated lightning impulse withstand voltage U:
- phase-to-phase, phase-to-earth, open contact gap
- across the isolating distance
   kV
   kV
60
70
75
85
Rated continuous current Ir 2) for busbar A 630                   630
for ring-main and cable feeders A 630                   630
for circuit-breaker feeders A 630  630 
50 Hz Rated short-time
withstand current Ik
for switchgear with t= 1 s up to kA 21  21 
for switchgear with t= 3 s 1) up to kA 21  21 
Rated peak withstand current Ip   up to kA 52.5  52.5 
Filling level Rated filling level pre  (absolute)                                               kPa 1.6  1.6 
(pressure values at 20 °C) Minimum functional level pme  (absolute)   kPa 1.5  1.5 
Ambient air temperature 3) Operation standard °C −25 to +55 −25 to +55
  on request °C −40 to +70 −40 to +70
  Storage/transport standard °C −25 to +55 −25 to +55
  on request °C −40 to +70 −40 to +70
Degree of protection for gas-filled switchgear vessel IP65 IP65
  for switchgear enclosure IP2X / IP3X 1) IP2X / IP3X 1)
  for low-voltage compartment IP3X / IP4X 1) IP3X / IP4X 1)
Partition class   PM PM
Loss of service continuity category Feeder panels with (switch-)disconnector LSC2 LSC2
Billing metering panel M, cable feeder K LSC1 LSC1
Accessibility to compartments Busbar compartment  
(enclosure) Switching-device compartment Non-accessible 
  Cable compartment
- Feeder panels with switching device
- Billing metering panel M, cable feeder K
Interlock-controlled 
   
Internal arc classification 4) IAC A  
(option) Accessibility FL or FLR  
  Arc test current IA                                                                                                          up to kA 21  21 
  Test duration tA                                                                                                                                                                                                                                                s
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier