Rated voltage | Ur | kV | 12 | 17.5 | 24 | |||||||
Rated frequency | Fr | Hz | 50 or 60 | 50 or 60 | 50 or 60 | |||||||
Insulation level | ||||||||||||
Industrial frequency 50Hz/1min Across isolating distance |
Ud | kV rms | 28 | 38 | 50 | |||||||
Ud | kV rms | 32 | 45 | 60 | ||||||||
Phase-to-phase, phase-to-earth Across isolating distance |
Up | kV peak | 75 | 95 | 125 | |||||||
Up | kV peak | 85 | 110 | 145 | ||||||||
Rated current | Ir | A | 630 | 630 | 400 | 400 | 630 | 630 | ||||
Rated current busbars | Ir | A | 630 | 630 | 400 | 400 | 630 | 630 | ||||
Rated peak current | Ip | kA | 62.5 | 52.5 | 31.25 | 40 | 40 | 50 | ||||
Short-time withstand current | It | kA rms | 25 | 21 | 12.5 | 16 | 16 | 20 | ||||
tk | s | 1 | 1 or 3 | 1 | 1 | 1 | 1 or 3 | |||||
Breaking capacity Active load Earth fault Cable charging |
Iload | A | 630 | 630 | 400 | 400 | 630 | 630 | ||||
Ief1 | A | 320 | 320 | 320 | 320 | 320 | 320 | |||||
Icc | A | 110 | 110 | 110 | 110 | 110 | 110 | |||||
Making capacity of switch and earthing switches | Ima | kA peak | 62.5 | 52.5 | 31.25 | 40 | 40 | 50 | ||||
Bushing (1) | Type | C | C | B or C | B or C | C | C | |||||
Mechanical endurance Switch disconnector | M1 | Number of | 1000 | 1000 | 1000 | |||||||
Earthing switch | openings | |||||||||||
M0 | Number of openings |
1000 | 1000 | 1000 | ||||||||
Electrical endurance Switch disconnector | E3 | Number of CO at rated |
100 | 100 | 100 | |||||||
Earthing switch | current | |||||||||||
Number of short-circuit making operations |
5 | 5 | 5 | 5 | 5 | 2 | ||||||
E2 | Number of short-circuit making operations |
5 | 5 | 5 | 5 | 5 | 2 |