a) Ambient temperature | ||||||
Maximum temperature | + 40 ºC | |||||
Maximum temperature (24-hour average) | + 35 ºC | |||||
Minimum temperature | - 15 ºC | |||||
Diurnal temperature differences | < 15K | |||||
b) Humidity | ||||||
Daily average relative humidity | ≤ 95% | |||||
Daily average water vapor pressure | ≤ 2.2 × 10 - 3 MPa; | |||||
Monthly average relative humidity | ≤ 90% | |||||
Average monthly water vapor pressure | ≤ 1.8 × 10 - 3 MPa | |||||
c) Altitude | ≤ 1000m | |||||
d) Seismic intensity | No more than 8 degrees | |||||
e) There is no dripping water, no flammable and explosive hazard, no chemical corrosive gas and no violent vibration in the place of use. |
Serial number | Projects | unit | Value | |||
1 | Rated voltage | kV | 12 | |||
2 | Rated short-time power frequency withstand voltage (1min) | 42 / 48(fracture) | ||||
3 | Rated lightning impulse withstand voltage (peak) | 75 / 85(fracture) | ||||
4 | Rated frequency | Hz | 50 | |||
5 | Current rating | A | 630 ~ 4000 | |||
6 | Rated short-circuit interrupting current | kA | 20 ,25 ,31.5 ,40 | |||
7 | Rated short-time withstand current | kA | 20 ,25 ,31.5 ,40 | |||
8 | Rated short-circuit duration | s | 4 | |||
9 | Rated peak withstand current | kA | 50 ,63 ,80 ,100 | |||
10 | Rated short-circuit closing current | kA | 50 ,63 ,80 ,100 | |||
11 | Power frequency withstand voltage of secondary circuit (1min) | V | 2000 | |||
12 | Rated single/back-to-back capacitor bank breaking current | A | 630 / 400 ( ≤ 31.5kA) 800 / 400 (40kA) |
|||
13 | The rated capacitor bank closes the inrush current | kA | 12.5 | |||
14 | Opening time (rated voltage) | ms | 20 ~ 50 | |||
15 | Closing time (rated voltage) | ms | 35 ~ 70 | |||
16 | Mechanical life | time | 20000 | |||
17 | The number of times the rated current is interrupted | 20000 | ||||
18 | Rated number of short-circuit current interruptions | 50 ( ≤ 31.5kA) 30(40kA) |
||||
19 | Dynamic and static contacts allow for wear and cumulative thickness | mm | 3 | |||
20 | Rated closing and opening operating voltage | V | AC110 / 220 DC110 / 220 | |||
21 | Rated voltage of energy storage motor | V | AC110 / 220 DC110 / 220 | |||
22 | Rated power of energy storage motor | W | 80 | |||
23 | Energy storage time | s | ≤ 15 | |||
24 | Contact opening distance | mm | 11 ± 1 | |||
25 | Contact stroke | mm | 3.1 ±0.3 ( ≤ 31.5kA) 3.5 ±0.5(40kA) |
|||
26 | Contact closing bounce time | ms | ≤ 2 | |||
27 | Three-phase splitting and closing, different periods | ms | ≤ 2 | |||
28 | Average opening speed | m / s | 0.9 ~ 1.5 | |||
29 | Average closing speed | m / s | 0.5 ~ 1.0 | |||
30 | Dominant electrical loop resistance | μΩ | ≤ 60 (630A) ≤ 45 (1250A) ≤ 35 ( 1600A ~ 2000A) ≤ 25 (2500A ) |
|||
31 | Rated sequence of operations | / | opening -0.3s- Combined -180s- Combined |