Technical data ANSI / IEEE Ratings | Special Ratings | |||||
Rated voltage | kV | 15 | 27 | 38 | ||
Maximum operating voltage | kV | 15 | 27 | 38 | 42 | |
Rated power frequency withstand voltage | kV | 36 | 60/125 | 80/200 | 85/200 | |
Rated lightning impulse withstand voltage | kV | 75 | 125 | 200 | 200 | |
Rated frequency | Hz | 60 | 60 | 60 | 60 | |
Rated busbar current 2) | A | ... 1200 … 2500 | ... 1250 … 2500 | ... 1250 … 2500 | ... 1250 … 2500 | |
Rated current of feeder | A | ... 1200 … 2500 | ... 1250 … 2500 | ... 1250 … 2500 | ... 1250 … 2500 | |
Rated peak withstand current | kA | … 104 | … 104 | … 104 | … 104 | |
Rated short-time current 3 s | kA | … 40 | … 40 | … 40 | … 40 | |
Internal Arc Classification 1) | IAC AFLR 40 kA 1s |