Customization: | Available |
---|---|
Certification: | VDE |
Shell Material: | Steel Plate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated voltage Rated power frequency withstand voltage - 1 min |
Ur Ud (3) |
kV kV |
12 28 |
17.5 38 |
24 50 |
||||
Rated lightening impulse withstand voltage - peak | Up | kV | 75 | 95 | 125 | ||||
Rated frequency | f | Hz | 50/60 | 50/60 | 50/60 | ||||
Rated short circuit breaking current | Isc | kA | up to 40 | up to 40 | up to 31.5 | ||||
Rated peak withstand current | Ip @50Hz | kA | 100 | 100 | 80 | ||||
Ip @60Hz | kA | 104 (2) | 104 (2) | 82 (2) | |||||
Rated duration of short circuit | tk | s | 3 | 3 | 3 | ||||
Rated current busbar, max | Irbb | A | up to 4000 (1) | up to 4000 (1) | up to 3150 (4) | ||||
Rated current circuit breaker | Ir | A | 630 | 630 | 630 | ||||
Ir | A | 1250 | 1250 | 1250 | |||||
Ir | A | 2000 | 2000 | 2000 | |||||
Ir | A | 2500 | 2500 | 2500 | |||||
Ir | A | 3150 | 3150 | 3150 (1) | |||||
Ir | A | 4000 (1) | 4000 (1) | ||||||
Rated current contactor (see detail in PIX-M) | Ir | A | 195 | NA | NA | ||||
Rated current switch disconnector | Ir | A | 630 | 630 | 630 | ||||
Rated current fused switch disconnector | Ir | A | 200 | 200 | 200 | ||||
Internal arc classification | |||||||||
Internal arc | Isc | kA | 40 | 40 | 31.5 | ||||
Arc duration | t | s | 1 | 1 | 1 | ||||
Classification | AFLR | AFLR | AFLR | ||||||
Degree of protection | |||||||||
Enclosure | StandardOption | IP3X | IP3X | IP3X | |||||
IP4X | IP4X | IP4X | |||||||
Between compartments | IP2X | IP2X | IP2X |