Customization: | Available |
---|---|
Breaking Capacity: | Medium Voltage |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ZW32-12 outdoor column vacuum circuit breaker (hereinafter referred to as circuit breaker) is rated voltage of 12kV, three-phase AC 50Hz outdoor power distribution equipment. It is mainly used to close the load current and break the overload current and short circuit in the power system Current. The circuit breaker can be used as a sectional switch on the 12kV distribution trunk line, branch line and ring network line of the city grid, as well as a section switch on the 12kV distribution trunk line, branch line and ring network line.It can be used as an incoming switch for rural power grids, industrial and mining enterprises, living quarters and construction sites
number | Projects | unit | data | |
1 | Rated voltage | kV | 12 | |
2 | Rated frequency | Hz | 50 | |
3 | Current rating | A | 630 | |
4 | Rated short-circuit interrupting current (RMS) | kA | 25 | |
5 | Rated peak withstand current (peak) | kA | 63 | |
6 | Rated short-time withstand current (4s) (RMS) | kA | 25 | |
7 | Rated short-circuit closing current (peak) | kA | 63 | |
8 | Mechanical life | time | 10000 | |
9 | Rated number of short-circuit breaking current interruptions | time | 30 | |
10 | Power Frequency Withstand Voltage (1min) :(RMS) Interphased, relative/fracture |
kV | 42/48 | |
11 | Interphased, relative/fracture" | kV | 75/85 | |
12 | Secondary circuit: 1min power frequency withstand voltage | V | 2000 |