Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
•C2-E2-M2-S2 level circuit breaker, designed according to international and domestic standards
Complete the type test
• Extended mechanical and electrical life, suitable for lines and cables
The system is also able to withstand higher transient recovery voltages
• Based on AB-B's continuous vacuum interrupting technology with extended electrical
life and extremely low heavy breakdown rate
• Simple and reliable spring operating mechanism reduces operating power and ensures an extended machine
Mechanical life
• Vacuum arc extinguishing to reduce environmental impact
• Electrical and mechanical anti-jumping
• Porcelain vase poles are suitable for outdoor harsh environments
• Meets automatic reclosing requirements
• Easy to install - height-adjustable mounting bracket
• The circuit breaker body is assembled and tested at the factory, reducing the need for on-site installers
The name of parameter | Unit | Parameter | |
Rated voltage | kV | 40.5 | |
Current rating | A | 1250/1600/2000/2500 | |
Power frequency withstand voltage vacuum fracture relative to ground/phase-to-phase | kV | 95 | |
95 | |||
Lightning impulse withstand voltage vacuum fracture relative to ground/phase | kV | 185 | |
185 | |||
Rated short-circuit interrupting current | kA | 31.5 | |
Rated short-circuit closing current | kA | 80 | |
Rated short-time withstand current | kA/s | 31.5/4 | |
Rated peak withstand current | kA | 80 | |
Closing and opening are of different periods | ms | 3 | |
Mechanical life | COs | ≥10000 | |
Rated sequence of operations | O-0.3 s-CO-180 s- CO | ||
Circuit breaker rating | C2 - E2 - M2-S2 1 )2) | ||
Operating mechanism | Spring-operated mechanism | ||
Rated capacitance opening and closing current | A | 800 | |
Creeping distance | mm/kV | ≥31 | |
Static terminal pull | longitudinal Transverse Vertical |
N | 750 |
500 | |||
750 | |||
Rated Inflation Pressure (N2, 20ºCAbsolute) | Bar | 1.6 ± 0.1 | |
Minimum maintenance inflation pressure (N2, 20ºC absolute) | Bar | 1.2 | |
Rated control voltage | DC110/220 V, AC220 V | ||
Rated energy storage voltage | DC110/220 V, AC220 V | ||
Quality (with standard bracket) | kg | ≤900 |