Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Common features | |||||||||
Rated operating voltage Ue | [V] | 690 | |||||||
Rated insulation voltage Ui | [V] | 1000 | |||||||
Rated impulse withstand voltage Uimp | [kV] | 12 | |||||||
frequency | [Hz] | 50 - 60 | |||||||
Number of poles | 3- 4 | ||||||||
type | Fixed/Drawable | ||||||||
Insulation characteristics | IEC 60947-2 | ||||||||
Emax 2 | E1.2 | ||||||||
Performance level | B | C | N | ||||||
Rated uninterruptible current Iu (40°C) | [A] | 630 | 630 | 250 | |||||
[A] | 800 | 800 | 630 | ||||||
[A] | 1000 | 1000 | 800 | ||||||
[A] | 1250 | 1250 | 1000 | ||||||
[A] | 1600 | 1600 | 1250 | ||||||
[A] | 1600 | ||||||||
[A] | |||||||||
The current carrying capacity of the N-pole of the 4-pole circuit breaker | [%Iu] | 100 | 100 | 100 | |||||
Rated limit short-circuit breaking capacity ICU | 400-415 V | [kA] | 42 | 50 | 66 | ||||
440 V | [kA] | 42 | 50 | 66 | |||||
500-525 V | [kA] | 42 | 42 | 50 | |||||
690 V | [kA] | 42 | 42 | 50 | |||||
Rated operating short-circuit breaking capacity ICS | [%Icu] | 100 | 100 | 100 1) | |||||
"Rated for short-term tolerance Current ICW | (1s) | [kA] | 42 | 42 | 50 | ||||
(3s) | [kA] | 24 | 24 | 30 | |||||
"Rated for short circuit on Capability (peak current) Icm" | 400-415 V | [kA] | 88 | 105 | 145 | ||||
440 V | [kA] | 88 | 105 | 145 | |||||
500-525 V | [kA] | 88 | 88 | 105 | |||||
690 V | [kA] | 88 | 88 | 105 | |||||
Category of use (according to IEC 60947-2) | B | B | B | ||||||
Breaking | Breaking time I< Icw | [ms] | 40 | 40 | 40 | ||||
Breaking time I>Icw | [ms] | 25 | 25 | 25 | |||||
size | H - Fixed/Drawable | [mm] | 296/363.5 | 296/363.5 | 296/363.5 | ||||
D - Fixed/Drawable | [mm] | 183/271 | 183/271 | 183/271 | |||||
W - Fixed 3-pole/4-pole/4-pole FS | [mm] | 210/280 | |||||||
W - Draw-out 3-pole/4-pole/4-pole FS | [mm] | 278/348 | |||||||
Weight (circuit breaker incl. trip and current sensor) | Stationary 3P/4P | kg | 14/16 | ||||||
"Draw-out 3-pole/4-pole/4-pole FS Fixed section included" | kg | 38/43 | |||||||
1) Ics : 50kA, suitable for 400V... 440V voltage; 2) Ics: 125kA, suitable for 400V... 440V voltage; 3) E4.2H 3200A:66 Icw(3s) | |||||||||
Emax 2 | E1.2 | ||||||||
Mechanical life (normal maintenance as required by the manufacturer Assignment) | [Iu] | ≤ 1000 | 1250 | 1600 | |||||
[Number of Cycles x 1000] | 20 | 20 | 20 | ||||||
frequency | [times/hour] | 60 | 60 | 60 | |||||
Electrical life (normal maintenance as required by the manufacturer Assignment) | 440 V | [Number of Cycles x 1000] | 8 | 8 | 8 | ||||
690 V | [Number of Cycles x 1000] | 8 | 65 | 65 | |||||
frequency | [times/hour] | 30 | 30 | 30 |