UniGear 500R isa veryspaceefficientsolution,designed toreduce the width of themedium-voltage air-insulated switchgear
Panel design isonly500mmwidefor feeder currentupto 2000 A
Its compact designmakesUniGear500R idealfor container installation forprimarydistribution
Units canbe coupled togetherdirectlywiththeotherproducts of theUniGear family
One of themain characteristicsof theUniGear500R switchgear is the isolation of thecircuit-breaker from themainbusbarsbymeans of thethree-position disconnector
Characteristics of UniGear 500R
Range • Upto17.5kV,…2000 A,…31.5kA • IECandENAstandards • Standard and customized versions Safety • Fitted withsafetyinterlocks •Visible earthing connection(IEC version) • Internal arc classificationIACAFLR(IEC)andIAC AFL(ENA) • Classified asLSC-2A,PM
Flexibility • Widerange of applications • Traditional andIEC 61850basedprotection andcontrol solutions • Ring core,block type instrumentstransformersorsensors