Customization: | Available |
---|---|
Breaking Capacity: | Medium Voltage |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product scope
Key benefits
Key features
Circuit breaker | HD4 12 | |||||||
Standards | IEC 62271-100 | • | ||||||
Rated voltage | Ur [kV] | 12 | ||||||
Rated insulation voltage | Us [kV] | 12 | ||||||
Withstand voltage at 50 Hz | Ud (1 min) [kV] | 28 | ||||||
Impulse withstand voltage | Up [kV] | 75 | ||||||
Rated frequency | fr [Hz] | 50-60 | ||||||
Rated normal current (40 °C) (1) | Ir [A] | 630 | 1250 | 630 | 1250 1600 1600 2000 2500 3150 3600 | |||
Rated breaking capacity | Isc [kA] | 16 | 16 | 16 | 16 - 16 - - - - | |||
25 | 25 | 25 | 25 - 25 25 25 25 25 | |||||
31.5 | 31.5 | 31.5 | 31.5 - 31.5 31.5 31.5 31.5 31.5 | |||||
- | - | - | - 40 - 40 40 40 40 | |||||
- | - | - | - 50 - 50 50 50 50 | |||||
Rated short-time withstand current (3 s) |
Ik [kA] | 16 | 16 | 16 | 16 - 16 - - - - | |||
25 | 25 | 25 | 25 - 25 25 25 25 25 | |||||
31.5 | 31.5 | 31.5 | 31.5 - 31.5 31.5 31.5 31.5 31.5 | |||||
- | - | - | - 40 - 40 40 40 40 | |||||
- | - | - | - 50 - 50 50 50 50 | |||||
Making capacity | Ip [kA] | 40 | 40 | 40 | 40 - 40 - - - - | |||
63 | 63 | 63 | 63 - 63 63 63 63 63 | |||||
80 | 80 | 80 | 80 - 80 80 80 80 80 | |||||
- 100 - 100 100 100 100 | ||||||||
- | - | - | - 125 - 125 125 125 125 | |||||
Operation sequence [O-0.3s-CO-15s-CO] | • | |||||||
Opening time [ms] | 35-60 | |||||||
Arcing time [ms] | 10-15 | |||||||
Total breaking time [ms] | 45-75 | |||||||
Closing time [ms] | ≤85 | |||||||
Weight [Kg] | 114 114 | 145 114 | 165 | |||||
Standardised table of dimensions | 1VCD000226 1VCD000231 | TN 7163 TN 7178 | TN 7165 | |||||
Absolute SF6 gas pressure (2) [kPa] | 380 (430 a 31.5 kA) | 380 | ||||||
Operating temperature [°C] | - 5 ... + 40 °C | |||||||
Tropicalization IEC: 60068-2-30, 60721-2-1 | • | |||||||
Electromagnetic compatibility IEC 62271-1 | • |