Customization: | Available |
---|---|
Certification: | VDE |
Shell Material: | Steel Plate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Electrical data of the switchgear | Rated voltage Ur | kV | 7.2 | 12 | ||
Rated insulation level | ||||||
Rated short-duration power-frequency withstand voltage Ud : - phase-to-phase, phase-to-earth, open contact gap - across the isolating distance |
kV kV |
20 23 |
28 32 |
|||
Rated lightning impulse withstand voltage Up : - phase-to-phase, phase-to-earth, open contact gap - across the isolating distance |
kV kV |
60 70 |
75 85 |
|||
Rated continuous current Ir 2) | for busbar | A | 630 630 | |||
for ring-main and cable feeders | A | 630 630 | ||||
for circuit-breaker feeders | A | 630 | 630 | |||
50 Hz | Rated short-time withstand current Ik |
for switchgear with tk = 1 s | up to kA | 21 | 21 | |
for switchgear with tk = 3 s 1) | up to kA | 21 | 21 | |||
Rated peak withstand current Ip | up to kA | 52.5 | 52.5 | |||
Filling level | Rated filling level pre (absolute) kPa | 1.6 | 1.6 | |||
(pressure values at 20 °C) | Minimum functional level pme (absolute) | kPa | 1.5 | 1.5 | ||
Ambient air temperature T 3) | Operation | standard | °C | −25 to +55 | −25 to +55 | |
on request | °C | −40 to +70 | −40 to +70 | |||
Storage/transport | standard | °C | −25 to +55 | −25 to +55 | ||
on request | °C | −40 to +70 | −40 to +70 | |||
Degree of protection | for gas-filled switchgear vessel | IP65 | IP65 | |||
for switchgear enclosure | IP2X / IP3X 1) | IP2X / IP3X 1) | ||||
for low-voltage compartment | IP3X / IP4X 1) | IP3X / IP4X 1) | ||||
Partition class | PM | PM | ||||
Loss of service continuity category | Feeder panels with (switch-)disconnector | LSC2 | LSC2 | |||
Billing metering panel M, cable feeder K | LSC1 | LSC1 | ||||
Accessibility to compartments | Busbar compartment | |||||
(enclosure) | Switching-device compartment | Non-accessible | ||||
Cable compartment - Feeder panels with switching device - Billing metering panel M, cable feeder K |
Interlock-controlled | |||||
Internal arc classification 4) | IAC A | |||||
(option) | Accessibility FL or FLR | |||||
Arc test current IA up to kA | 21 | 21 | ||||
Test duration tA s | 1 | 1 |