Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Applications
HD4 circuit breakers can be used to control and protect lines in power distribution systems,power equipment, etc., especially suitable for those who require a special level of dielectric strength Other sensitive occasions, such as capacitor banks, compensating reactors, etc.
Installation:
The HD4 circuit breaker operating mechanism is arranged on the front side, There are two installation methods,it is fixed and can be withdrawn
standard:
HD4 circuit breaker conforms to GB/T 1984 and other relevant standards, and has passed The following tests are carried out to ensure safety under any normal installation conditions Serve reliably
HD4/Z | ||||||||||
standard | GB/T 1984 IEC 62271-100 |
|||||||||
Rated voltage | Ur[kV] | 40.5 | ||||||||
Rated insulation voltage | Us[kV] | 40.5 | ||||||||
Power frequency withstand voltage | Ud(1 min) [kV] | 95(1) | ||||||||
Withstand voltage for lightning impulses | Up[kV] | 185(1) | ||||||||
Rated frequency | Fr[Hz] | 50 | ||||||||
Rated Current(2) | Ir[A] | 1250 1600 2000 2500 3150(3) | ||||||||
Rated short-circuit interrupting current | Isc[kA] | 25 31.5 | ||||||||
Rated short-time withstand current (4 s) | Ik[kA] | 25 31.5 | ||||||||
Rated short-circuit closing current | Ip[kA] | 63 80 | ||||||||
Rated sequence of operations | [O-0.3 s-CO-180 s-CO] | |||||||||
Opening time | [ms] | 35~65 | ||||||||
Arc time | [ms] | ≤15 | ||||||||
Interrupting time | [ms] | 40~80 | ||||||||
Closing time | [ms] | 60~100 | ||||||||
Maximum external dimensions | H[mm] 1575 | |||||||||
L[mm] 895 | ||||||||||
D[mm] 720 | ||||||||||
weight | [kg] | 280 280 350 350 350 | ||||||||
Pole SF6 gas pressure (absolute) | [kPa] | 550 | ||||||||
Pole SF6 gas alarm pressure (absolute) | [kPa] | 480 | ||||||||
Operating ambient temperature | [ºC] | -5~+40(4) |