Aeg B2 Plus G-15 Generator Vacuum Circuit Breaker

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Energy-storage Type
Gold Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Fast Delivery
The supplier can deliver the goods within 15 days
Customization from Designs
The supplier provides design based customization services
ODM Services
The supplier provides ODM services
Management Certification
The supplier has quality management system certification, including:
ISO9001:2015 certificate
ISO45001:2018 certificate
ISO14001
to see all verified strength labels (14)
  • Aeg B2 Plus G-15 Generator Vacuum Circuit Breaker
  • Aeg B2 Plus G-15 Generator Vacuum Circuit Breaker
  • Aeg B2 Plus G-15 Generator Vacuum Circuit Breaker
Find Similar Products
  • Overview
  • Product Description
  • Product Photos
  • Product Parameters
Overview

Basic Info.

Model NO.
B2 Plus G-15
Speed
Normal Type Circuit Breaker
Arc-extinguishing Medium
Vacuum
Installation
Fixed
Structure
Vcb
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker
Certification
VDE
Rated Voltage
15kv
Current Rating
2500/3150/4000/5000
Rated Power Frequency Withstand Voltage
42kv
Rated Frequency
50/60Hz
Transport Package
Carton for Export
Specification
100kg
Trademark
AEG
Origin
China

Product Description

Product Description

Faults that occur near a generator power supply are more demanding than the fault conditions in a normal distribution circuit. Due to these special fault characteristics, special vacuum circuit breakers suitable for the protection of generators need to be specially designed and developed. The VB2 PlusG generator outlet vacuum circuit breaker meets the double international standard of IEC/IEEE 62271-37-013 and has passed a full set of type tests in the KEMA laboratory.Faults that occur near a generator power supply are more demanding than the fault conditions in a normal distribution circuit. Due to these special fault characteristics, special vacuum circuit breakers suitable for the protection of generators need to be specially designed and developed. The VB2 PlusG generator outlet vacuum circuit breaker meets the double international standard of IEC/IEEE 62271-37-013 and has passed a full set of type tests in the KEMA laboratory.
 

Product Photos

Aeg B2 Plus G-15 Generator Vacuum Circuit BreakerAeg B2 Plus G-15 Generator Vacuum Circuit BreakerAeg B2 Plus G-15 Generator Vacuum Circuit Breaker

Product Parameters
Project Unit Parameter
Rated voltage kV 15 
Current rating A 2500/3150/4000/5000
Rated power frequency withstand voltage (1min) kV 42 
Rated lightning impulse withstand voltage kV 95 
Rated frequency Hz 50/60
Rated short-circuit interrupting current kA 31.5/40/50
Rated short-time withstand current (3s) kA 31.5/40/50
Rated peak withstand current kA 86.3/110/137
Rated short-circuit closing current kA 86.3/110/137
Rated sequence of operations   CO-30min-CO
Mechanical life time 10000 
DC component % 75%
Transient recovery voltage peaks kV 27 (system source, generator source)
39 (out-of-step interrupting)
Transient recovery voltage rise rate kV/μs 3.5 (System Source)
3.5 (Generator Source)
3.3 (Out-of-Step Interrupting)

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier