Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MPP-S16A pole mounted load break switch is used for breaking rated voltage 12/24/40.5kV,rated current 630A,50/60Hz power distribution system, closing load current and over load current of power system, it could separate automatically track sections of power distribution which faults occur. The switch is matched with electronic controller which is with the latest technology. The switch has manual, motor, remote operation modes. The electronic controller would be installed inside the stainless steel box, so it could be used in various climate conditions. Besides that, the wire/wireless modem installed inside control box could achieve remote monitoring and controlling. It's easy and convenient for installation the switch on pole, and that could reduce the execution cost.
Products Type | PGS-12 | PGS-24 | PGS-40.5 | |||
Basic Ratings | ||||||
Maximum System Voltage | 15 kV | 25.8 kV | 40.5 kV | |||
Rated Continuous Current | 630 A | 630 A | 630 A | |||
Rated Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | |||
Short Time Withstand Current ( rms) | 20 kA/ 4sec | 25kA/ 1sec | 20 kA/1 sec | |||
Making and Breaking Capacity | ||||||
Mainly Active Load Current | 630A | 630A | 630A | |||
Number of Load-break Operations | 400 times | 400 times | 400 times | |||
Short-circuit Making Current (peak) | 50 kAp | 50kAp | 50 kAp | |||
Number of Making Operations | 5 times | 5 times | 5 times | |||
Cable Charging Current | 25A | 25A | 25 A | |||
Line Charging Current | 1.5A | 1.5A | 2A | |||
Closed Loop Circuit Current | 630 A | 630 A | 630 A | |||
Transformer Magnetizing Current | 22A | 22A | 22A | |||
Power Frequency Withstand Current Test | ||||||
7 | ||||||
Wet Condition- 10 sec Ph-Eth, Across Interrupters) |
(Ph- Ph, |
45 kV | 50kV | 70 kV | ||
Dry Condition - 1 min) Earth, Phase to Earth) |
(Phase to |
50 kV | 60kV | 95 kV | ||
Dry Condition - 1 min Interrupter ) |
( Across |
50 kV | 60kV | 110 kV | ||
Impulse Withstand Current Test ( 1.2 x 50 μs ) | ||||||
Phase to Phase, Phase to Eart | 85 kV | 150kV | 195 kV | |||
Across Interrupter | 95 kV | 150kV | 215 kV | |||
Other Ratings & Specifications | ||||||
Internal Arc Test | 20kA /0.1 sec | 20kA /0.1 sec | 20kA /0.1 sec | |||
Arc Extinction Medium | SF 6 Gas | SF 6 Gas | SF 6 Gas | |||
Insulation Medium | SF 6 Gas | SF 6 Gas | SF 6 Gas | |||
Creepage Distance (Porcelain) | 550 mm | 840 mm | 1055 mm | |||
Creepage Distance (Silicon) | 615 mm | 900 mm | 1250mm | |||
IP Level | 54 | 54 | 54 | |||
Operation Performance | ||||||
Closing/Opening Time | < 0.1 sec | < 0.1 sec | < 0.7 sec | |||
Mechanical Operations (Guaranteed) | 10,000 times | 10,000 times | 10,000 times | |||
Operating Temperature (*Manual Type) | -25 (-40) ~ 70ºC | -25 (-40) ~ 70ºC | - 25 (-40)~ 70ºC | |||
Gas Pressure | ||||||
Nominal Pressure (kgf/cm2 G, at 20°C)) | 0.7 | 1.0 | 1.0 | |||
Bursting Pressure (kgf/cm2 G) |
4 ~ 6 | 4 ~ 6 | 4 ~ 6 |