Customization: | Available |
---|---|
Breaking Capacity: | Medium Voltage |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated voltage | Ur | kV | 12 | ||||||||
Rated frequency | fr | Hz | 50/60 | ||||||||
"Rated for short time power frequency Withstand voltage (1min)" |
interphase and to ground | Ud | kV | 42 | |||||||
Vacuum breaks | kV | 48 | |||||||||
Rated for lightning strike tolerance voltage |
interphase and to ground | Up | kV | 75 | |||||||
Vacuum breaks | kV | 85 | |||||||||
Rated sequence of operations | O-0.3s-CO-15s -CO | ||||||||||
Phase spacing | mm | 150 | 210 | 275 | |||||||
Rated short-circuit interrupting current | Isc | kA | 25 | 31.5 | 25 | 31.5 | 40 | 25 | 31.5 | 40 | |
Rated continuous current | Ir | 630A | . | . | . | . | |||||
1250A | . | . | . | . | . | . | |||||
1600A | . | . | . | . | . | . | |||||
2000A | . | . | . | . | . | . | |||||
2500A | . | . | . | ||||||||
3150A | . | . | . | ||||||||
40002) A | . | . | . | ||||||||
Rated short-time withstand current | Ik | kA | 25 | 31.5 | 25 | 31.5 | 40 | 25 | 31.5 | 40 | |
Rated short-circuit duration | tk | s | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | |
Rated peak withstand current | Ip | kA | 63 | 80 | 63 | 80 | 125 | 63 | 80 | 125 | |
The DC component of the rated short-circuit interrupting current | Pcs | 52% | |||||||||
The DC time constant of the rated short-circuit interrupting current | τ | ms | 45 | ||||||||
Opening time | ms | 20...45 | |||||||||
Closing time | ms | 36...60 | |||||||||
Rated cable charging breaking current | Ic | A | 25 | ||||||||
Rated line charging interrupting current | Il | A | 10 | ||||||||
Rated back-to-back capacitor bank interrupting current | lbb | A | 800 | ||||||||
Rated back-to-back capacitor bank shut-off inrush current (inrush frequency) | lbi | kA | 20(4250 Hz) | ||||||||
Mechanical life | time | 50000(≤1250A and ≤31.5kA) 30000(≥1600A and 1250A 40kA) |
|||||||||
Electrical life | Rated number of continuous current interruptions | time | 50000(≤1250A and ≤31.5kA) 30000(≥1600A and 1250A 40kA) |
||||||||
Rated short-circuit breaking The number of times the current is interrupted |
time | 100 | |||||||||
Circuit breaker rating | C2-E2-M2 |