Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Steel Plate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | C Model | F Model | V Model | CB Model | |||
Loadswitch | VCB | disconector / earth switch | VCB | disconector / earth switch | |||
Rated voltage | kV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 |
power frequency withstand voltage( phase to phase /to the ground ) | kV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
Lightning impluse withstand voltage | kV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated current | A | 630 | 630 | 1250/630 | |||
Rated closed-loop interrupting current | A | 630 | |||||
Rated cable charging breaking current | A | 135/135 | |||||
Rated short-circuit closing current ( peak ) | A | 50 | 80 | ||||
Rated peak withstand current | kA | 50 | |||||
Rated short-time withstand current | kA/3s | 20 | |||||
Rated short-circuit opening current | kA | 31.5 | 20 | 25 | |||
Rated transfer current | A | 1750 | |||||
Equipped with fuse maximum current | A | - | 125 | ||||
Loop resistance | -n | ≤300 | ≤600 | ||||
Machanical life | time | 5000 | 3000 | 5000 | 2000 | 5000 | 500 |