Technical data | |||
Type | NXB&NXBD | ||
Rated Voltage | kV | 12 | 24 |
Power frequency withstand voltage,50Hz | |||
-to earth and between phases | kV | 28 | 50 |
-across the isolating distance | kV | 32 | 60 |
Lightning impulse withstandvoltage | |||
-to earth and between phases | kV | 75 | 125 |
- across the isolating distance | kV | 85 | 145 |
Currentratings | |||
Rated normal current | A | 630 | 630 |
Mainly active load breaking current | A | 630 | 630 |
Number of breaking operations co | n | 400 | 400 |
Line-charging breaking current | A | 50 | 50 |
Cable-charging breaking current | A | 50 | 50 |
Earth fault breaking current | A | 50 | 50 |
Cable charging breaking current under earth fault conditions | A | 29 | 29 |
No-load transformer breaking current | A | 63 | 63 |
Short-circuit ratings | |||
Short-time withstand current,lk/time | kA | 20/35 | 20/35 |
Peak withstand current | kA | 50 | 50 |
Short-circuit making current | kA | 50 | 50 |
Number of making operations | |||
-main switch (CL E3) | n | 5 | 5 |
-earthing switch 50kA(CLE2) | n | 3 | 3 |
-earthing switch 31,5kA(CL E3) | n | 5 | 5 |
Creepage distance | mm | 620 | 620/960 |
Mechanical endurance Co | n | 5000 | 5000 |
Ambient air temperature limits | oC | -40;+60 | -40;+60 |
Standards | IEC62271-1;IEC62271-102;IEC 62271-103 |