Standards | Low Voltage Switchgear and Controlgear Assemblies - Verification by testing* |
IEC 61439-1/-2 | |
Test certificates | ASTA, Great-Britain (resist. to accidental arcs acc . to IEC 61641 and IEC 60298, Appendix AA) DLR German Research Institute for Aerospace e . V. Jülich, Earthquake Test for Security Areas in Nuclear Power Stations IABG Industrieanlagen Betriebsgesellschaft, Vibration and shock tests Complying with Germanischer Lloyd, Hamburg |
||
Electrical data | Rated voltages | Rated insulation voltage Ui | 1000 V 3~, 1500 V- ** |
Rated operating voltage Ue | 690 V 3~, 750 V-** | ||
Rated impulse withstand voltage Uimp | 6 / 8 / 12 kV ** | ||
Overvoltage category | II / III / IV ** | ||
Degree of pollution | 3 | ||
Rated frequency | up to 60 Hz | ||
Rated current | Copper Busbars: | ||
Rated current Ie | up to 6300 A | ||
Rated peak withstand current Ipk | up to 250 kA | ||
Rated short-time withstand current Icw | up to 100 kA | ||
Copper Distribution bars: | |||
Rated current Ie | up to 2000 A | ||
Rated peak withstand current Ipk | up to 176 kA | ||
Rated short-time withstand current Icw | up to 100 kA | ||
Arc Fault Containment | Rated operational voltage | up to 690 V | |
Prospective short-circuit current | up to 100 kA | ||
Duration | 300 ms | ||
Criteria (IEC 61641) | 1 to 7 | ||
Forms of separation | up to Form 4 | ||
Mechanical characteristics |
Dimensions | Cubicles and frame | DIN 41488 |
Recommended height | 2200 mm | ||
Recommended width | 400, 600, 800, 1000, 1200 mm | ||
Recommended depth | 400, 600, 800, 1000, 1200 mm | ||
Basic grid size | E = 25 mm acc . to DIN 43660 | ||
Degrees of Protection | According to IEC 60529 | External from IP 30 to IP 54 Internal from IP 2X |
|
Steel components | Frame, incl. internal subdivisions | 2.0 / 2.5 mm | |
Cladding, internal | 1.5 / 2.0 mm | ||
Cladding, external | 1.5 mm | ||
Surface protection/Paint | Frame, incl. internal subdivisions | Zinc or Alu-zinc coated | |
Cladding, internal | Zinc or Alu-zinc coated | ||
Cladding, external | Zinc or Alu-zinc coated and Powder coated RAL 7035 (light grey) |
||
Plastic components | Halogen-free, self-extinguishing, flame retardant, CFC-free | IEC 60707, DIN VDE 0304 part 3 | |
Optional Extras, available on request |
Busbar system | Busbars | Fully insulated with heat shrinkable sleeving Silver plating Tin plating |
Special qualification | Test certificates | See test certificates listed above | |
Paint | Enclosure | Special colours on request |